Description
Automatic reclosing device
Code
ReStart Rm 2P
Suitable for
RCBO's MDC - 1P+N/2P - 30 mA
Rated voltage AC
230 V
Rated current
6 - 10 - 13 - 16 - 20 -25 - 32 A
No. modules
1
Standard
EN 50557
Rated frequency (Hz)
50 - 60 Hz
Distribution system
TT - TN-S
Rated non-operating resistance between live parts and earth (Rdo)
8kΩ
Insulation voltage (Ui)
500 V
Rated operating resistance between live parts and earth (Rd)
16 kΩ
Rated impulse withstand voltage (Uimp)
4 kV
Maximum operating frequency
30 oper./h
Overvoltage category
III
Mechanical endurance
4000
Dielectric strength test voltage between pole and earth
2500 Vac for 1 minute
Type of residual current protection
AC - A - A[IR] - F
Rated residual operating current
30 mA
Operating temperature
-5°C ÷ +40°C
Stocking temperature
-40°C ÷ +70°C
Automatic reclosure for untimely tripping
Yes
Earth failure test
Yes
Continuous system monitoring
No
Number of poles
2P
Electrocod
1414
Ware Number
85362010