RESTART WITH AUTOTEST PRO - COUPLED WITH RCCB'S - 2 POLES - 25 A TYPE A[IR] Idn=0,03 A 230 V ac - 5 MODULES EN 50022

Kód: GW90901N
Řada: 90 ReStart Range
Automatic reclosing devices
In the event the switch trips, the ReStart devices, after checking the system status, restore the power supply thereby ensuring maximum continuity of service in complete safety.
Available for both residual current circuit breakers and residual current circuit breakers with overcurrent protection, the range is characterized by the Autotest functions, with periodic and automatic control of the residual current protection without interrupting the power supply and PRO with extended control of the system.

Technické informace

Informace
Stáhnout
Certifikáty
Description Automatic reclosing device
Code ReStart Autotest PRO 2P
Rated voltage AC 230 V
Rated current 25 A
No. modules 5
Standard EN 50557, EN 61008-1
Rated frequency (Hz) 50Hz
Distribution system TT - TN-S
Rated non-operating resistance between live parts and earth (Rdo) 8kΩ
Insulation voltage (Ui) 500 V
Rated operating resistance between live parts and earth (Rd) 16 kΩ
Rated impulse withstand voltage (Uimp) 4 kV
Maximum operating frequency 30 oper./h
Overvoltage category III
Mechanical endurance 4000
Dielectric strength test voltage between pole and earth 2500 Vac for 1 minute
Type of residual current protection A[IR]
Rated residual operating current 30 mA
Operating temperature -25 +60 °C
Stocking temperature -40°C ÷ +70°C
Type of contacts Photomos (potential free)
Voltage operating 5-230 V ac/dc
Current operating 0.6mA (min)-100mA cosφ=1 (max)
Operating frequency 50 Hz
Use category AC12
Operating modes NO/NC/NC + pulse
Rated tightening torque 0,4 Nm
Terminal section ≤ 2,5 mm²
Automatic reclosure for untimely tripping Yes
Earth failure test Yes
Continuous system monitoring Yes
Autotest (automatic RCCB protection test) Yes
Completeable
with
GW90992 RS485 BUS Module
Number of poles 2P
Electrocod 1414
Ware Number 85362010

Product Data Sheet

User guide

Technical characteristics - IT

Technical characteristics - DE

Technical characteristics - EN

Technical characteristics - ES

Reach Declaration

Display the certificate

CE marking

VYBAVENÍ A POZNÁMKY
CHARACTERISTICS: after RCCB has tripped, ReStart checks the insulation prior to the automatic reclosure. In the event of a fault (earth leakage), ReStart will not reset the circuit breaker but will continue to monitor the circuit every 2 minutes reclosing the circuit breaker when safe to do so. In the meantime the integrated configurable auxiliary contact will change state to indicate that the automatic reset did not take place.
Compatible with:
-GW90992 ModBus RS485 interface module.
NOTE: the Autotest function automatically and periodically (every 28 days) tests the RCCB, without interrupting the electric power supply, thus maintaining the performance of the residual current protection over time.
230 V ac power supply, phase-neutral.
RCCB's type B and A[IR] Impulse Resistant presents greater resistance to untimely tripping in comparison to standard residual current circuit breakers. Immunity level 8/20µs: 3000A for IR type, 250A for standard type.
služby

Potřebujete technickou pomoc?

Obraťte se na nás a získejte odpovědi na své otázky: otázky týkající se zařízení, předpisů nebo produktů.

Najít Gewiss

Hledáte instalačního technika nebo prodejní místo?

Najděte důvěryhodného prodejce nebo instalačního technika.

Napište nám

Potřebujete informace o produktech nebo službách společnosti Gewiss?