Description
Interruttore automatico scatolato
Code
MSXD 125
No. of poles
3P+N
Rated current
50 A
Release
Electromechanic
ELECTRICAL CHARACTERISTICS
-
MECHANICAL CHARACTERISTICS
-
Standard
IEC/EN 60947-2
Execution
Fixed
Use category
A
DIN rail mounting
Yes, by means of accessory
Rated frequency (Hz)
50 / 60
Can be equipped with motor operator
Yes
Rated operating voltage (Ue)
525 Vac
Compatible interlock
-
Rated impulse withstand voltage (Uimp)
8 kV
Terminals supplied
Front FC
Overvoltage category
IV
Assembly position
Any
Insulation voltage (Ui)
525 V
Upline/downline power supply
Yes
Thermal regulation
0,63 - 0,8 - 1 x In
Electrical life (415Vac)
30.000 cycles
Magnetic regulation
Fixed - 500 A
Mechanical life
30.000 cycles
Neutral protection
Not protected
Operating temperature
-5°C +65°C
Total power loss
19.92 W
Stocking temperature
-20° +65°
Rated short-circuit current making capacity (Icm)
-
Weight (kg)
1.4
Rated short-time withstand current for 0,3s (Icw)
-
Width
120 mm
Idn regulation
0,03 - 0,1 - 0,3 - 0,5 - 1 - 3 A
Height
155 mm
DT regulation
0 - 60 - 200 - 400 - 700 ms
Depth
68 mm
SERVICE BREAKING CAPACITY (ICU)
-
RATED BREAKING CAPACITIY (ICS)
-
220/240Vac
50 kA
220/240Vac
50 kA
400/415Vac
36 kA
400/415Vac
36 / 30 kA
440Vac
25 kA
440Vac
25 kA
525Vac
22 kA
525Vac
22 kA
690Vac
-
690Vac
-
250Vdc
-
250Vdc
-
Ware Number
85362010