Description
Interruttore automatico scatolato
Code
MSX 400
No. of poles
4P
Rated current
400 A
Release
Electromechanic
ELECTRICAL CHARACTERISTICS
-
MECHANICAL CHARACTERISTICS
-
Standard
IEC/EN 60947-2
Execution
Fixed - Plug-in
Use category
A
DIN rail mounting
No
Rated frequency (Hz)
50 / 60
Can be equipped with motor operator
Yes
Rated operating voltage (Ue)
690 Vac - 250 Vdc
Compatible interlock
Lever – Cable
Rated impulse withstand voltage (Uimp)
8 kV
Terminals supplied
Front FC
Overvoltage category
IV
Assembly position
Any
Insulation voltage (Ui)
800 V
Upline/downline power supply
Yes
Thermal regulation
0,63 - 0,8 - 1 x In
Electrical life (415Vac)
4.500 cycles
Magnetic regulation
6 - 8 - 10 - 12 x In
Mechanical life
15.000 cycles
Neutral protection
100% x Ir
Operating temperature
-5°C +65°C
Total power loss
89.5999999999999 W
Stocking temperature
-20° +65°
Rated short-circuit current making capacity (Icm)
-
Weight (kg)
5.6
Rated short-time withstand current for 0,3s (Icw)
-
Width
185 mm
Idn regulation
-
Height
260 mm
DT regulation
-
Depth
103 mm
SERVICE BREAKING CAPACITY (ICU)
-
RATED BREAKING CAPACITIY (ICS)
-
220/240Vac
85 kA
220/240Vac
85 kA
400/415Vac
50 kA
400/415Vac
50 kA
440Vac
45 kA
440Vac
45 kA
525Vac
30 kA
525Vac
30 kA
690Vac
20 kA
690Vac
15 kA
250Vdc
40 kA
250Vdc
40 kA
Ware Number
85362010