MSXD 160 - MCCB WITH RESIDUAL CURRENT PROTECTION - THERMAL ADJUSTABLE - FIXED MAGNETIC - ADJUSTABLE RESIDUAL CURRENT RELEASE - 36kA 3P+N 160A 525V

Code: GWD9277

Range: MSX
Moulded case circuit breaker for power distribution

The moulded case circuit breakers MSX range is made up of circuit breakers with thermo-magnetic release, circuit breakers with thermo-magnetic release and Overcurrent Protection, circuit breakers with electronic release and switch disconnectors.

Technical Info

Information
Download
Software
Certificates
Description Interruttore automatico scatolato
Code MSXD 160
No. of poles 3P+N
Rated current 160 A
Release Electromechanic
 ELECTRICAL CHARACTERISTICS -
MECHANICAL CHARACTERISTICS -
Standard IEC/EN 60947-2
Execution Fixed
Use category A
DIN rail mounting Yes, by means of accessory
Rated frequency (Hz) 50 / 60
Can be equipped with motor operator Yes
Rated operating voltage (Ue) 525 Vac
Compatible interlock -
Rated impulse withstand voltage (Uimp) 8 kV
Terminals supplied Front FC
Overvoltage category IV
Assembly position Any
Insulation voltage (Ui) 525 V
Upline/downline power supply Yes
Thermal regulation 0,63 - 0,8 - 1 x In
Electrical life (415Vac) 10.000 cycles
Magnetic regulation Fixed - 2.080 A
Mechanical life 10.000 cycles
Neutral protection Not protected
Operating temperature -5°C +65°C
Total power loss 48.12 W
Stocking temperature -20° +65°
Rated short-circuit current making capacity (Icm) -
Weight (kg) 1.9
Rated short-time withstand current for 0,3s (Icw) -
Width 140 mm
Idn regulation 0,03 - 0,1 - 0,3 - 0,5 - 1 - 3 A
Height 165 mm
DT regulation 0 - 60 - 200 - 400 - 700 ms
Depth 68 mm
SERVICE BREAKING CAPACITY (ICU) -
 RATED BREAKING CAPACITIY (ICS)  -
220/240Vac 65 kA
220/240Vac 65 kA
400/415Vac 36 kA
400/415Vac 36 kA
440Vac 25 kA
440Vac 25 kA
525Vac 25 kA
525Vac 25 kA
690Vac -
690Vac -
250Vdc -
250Vdc -
Ware Number 85362010

Product Data Sheet

Information and general recommendations

User guide

Technical characteristics - IT

Technical characteristics - EN

Brochure - EN

Brochure - IT

Technical characteristics - ES

AUTOCAD Plugin

Plugin with GEWISS products for the software AUTOCAD®

Show more

PBT-Q

Low voltage systems and boards

Show more

PROJEX

Low voltage system design

Show more

PRICE

Estimation of electrical systems

Show more

CADpro

Advanced design of electrical systems

Show more

CE marking

EQUIPMENT AND NOTES
NOTES: for mounting on EN 50022 DIN rail, choose the fixing bracket GWD8876.
The space taken up on the EN 50022 DIN rail is approximately 8 modules.
ACCESSORIES SUPPLIED: supplied with front terminals (FC). 
CHARACTERISTICS: Adjustable thermal release Ir = 0.63 ÷ 1 x In
Fixed magnetic release Ii = 13 x ln
Residual current circuit breaker tripping (Idn) and delay (dt) thresholds are adjustable:
Idn (A): 0.03 - 0.1 - 0.3 - 0.5 - 1 - 3
dt (ms): 0 - 60 - 200 - 400 - 700
services

Do you need technical assistance?

Contact us to get the answers to your questions: plant, regulatory or product questions.

Find Gewiss

Are you looking for an installer or a sales point?

Find your trusted dealer or installer.

Write to us

Do you need information on Gewiss products or services?