Description
Motor switch
Rated operating voltage (Ue)
220 … 690 V AC
Rated frequency (f)
50/60 Hz
Rated operating current (Ie)
2.5 A
Setting range (It)
1,6...2,5 A
Number of poles
3P
No. modules
2.5
ELECTRICAL CHARACTERISTICS
-
MECHANICAL FACTS
-
Standard
IEC/EN 60947-2
Mounting position
Any
Insulation voltage (Ui)
690 V
Mechanical endurance (O-C cycle number)
100000
Rated impulse withstand voltage (Uimp)
6 kV
Electrical endurance (O-C cycle number)
100000 (AC-3)
Overvoltage category
III
IP degree
IP20
Short circuit breaking capacity (Icu)
100 kA (5kA 690V)
Pollution rating
3
Short circuit breaking capacity (Ics)
100 kA (5kA 690V)
Section rigid cable
<=10 mm²
Max. back-up fuse, if Icp > Icu
16kA 690V
Section flexible cable
<=6 mm²
Power dissipation per pole
2,5 W
Max. conductor stripping length
10 mm
PROTECTIONS
-
Rated tightening torque
2 Nm
Type of protection
Thermo magnetic
Operating temperature
-25 +60 °C
Tripping indication
The trip of the protection is signalled by the intermediate
position of the START and STOP buttons
Stocking temperature
-25 +70 °C
Ware Number