Description
Automatic reclosing device
Code
ReStart Autotest PRO 4P
Rated voltage AC
400 V
Rated current
63 A
No. modules
7
Standard
EN 50557, EN 61008-1
Rated frequency (Hz)
50Hz
Distribution system
TT - TN-S
Rated non-operating resistance between live parts and earth (Rdo)
8kΩ
Insulation voltage (Ui)
500 V
Rated operating resistance between live parts and earth (Rd)
16 kΩ
Rated impulse withstand voltage (Uimp)
4 kV
Maximum operating frequency
30 oper./h
Overvoltage category
III
Mechanical endurance
4000
Dielectric strength test voltage between pole and earth
2500 Vac for 1 minute
Type of residual current protection
A[IR]
Rated residual operating current
30 mA
Operating temperature
-25 +60 °C
Stocking temperature
-40°C ÷ +70°C
Type of contacts
Photomos (potential free)
Voltage operating
5-230 V ac/dc
Current operating
0.6mA (min)-100mA cosφ=1 (max)
Operating frequency
50 Hz
Use category
AC12
Operating modes
NO/NC/NC + pulse
Rated tightening torque
0,4 Nm
Terminal section
≤ 2,5 mm²
Automatic reclosure for untimely tripping
Yes
Earth failure test
Yes
Continuous system monitoring
Yes
Autotest (automatic RCCB protection test)
Yes
Completeable
with
GW90992 RS485 BUS Module
Number of poles
4P
Electrocod
1414
Ware Number
85362010