Description
Relais différentiel à tore séparé
Type
B
Dimension
3 modules
Norme
EN 60947-2 Annex M
Red LED report
Exceeding the threshold IΔn after the delay time Δt
Rated operating voltage (Ue)
230 V ca
Green LED report
Device properly powered
Operating voltage range
0,85 x Ue - 1,1 x Ue
Blinking green LED report
Exceeding the IΔn pre-alarm threshold
Fréquence nominale (Hz)
50 Hz / 60 Hz
Local reset
Oui
Regulation of IΔn
0,03 - 0,1 - 0,3 - 0,5 - 1 - 3 - 5 - 10 A
Remote Reset
Oui
Regulation of delay time Δt
0,1 - 0,2 - 0,3 - 0,4 - 0,5 - 0,75 - 1 - 5 - 10 s
Local test
Oui
Classe isolement
II
Alarm output contact type
Changeover (250 V - 10A - AC1)
Rated operating voltage with reference to the controlled circuit (Un)
400V ca
Fault output contact type
Changeover (250 V - 10A - AC1)
Rated insulation voltage with reference to the controlled circuit (Ui)
0,72 kV
Minimum switchable load of output contact
300 mW (5 V / 5 mA)
Rated impulse withstand voltage with reference to the controlled circuit (Uimp)
4 kV (cat. III)
Maximum cable section (rigid/flexible)
2,5 mm²
Rated insulation voltage with reference to the voltage source (Ui)
300V
Tightening torque
0,5 Nm
Rated impulse withstand voltage with reference to the voltage source (Uimp)
4 kV (cat. III)
Température de fonctionn.
-5°C +40°C (average ≤ 35 °C / 24 h)
Rated short-time withstand current (Icw)
40 kA (0,5 s)
Température de stockage
-25 °C +55 °C (+70 °C < 24 h)
Rated short-time withstand residual current (IΔw)
40 kA (0,5 s)
Humidité
5 % ÷ 90 %
-
-
Maximum installation altitude
2.000 m
Ware Number
85364900